For maintenance teams managing moisture in gas-insulated equipment, maintaining availability is a key consideration.
EMT Gas-Dry brings together a simple operating approach, measured field evidence and flexible configurations.
PASSIVE DRYING. ACTIVE PROTECTION.
Gas-Dry connects to the equipment filling port and passively removes moisture from SF₆ and Dry Air insulated gas compartments, without gas carts or de-energising the circuit.
MEASURED REDUCTION. OPERATIONAL ASSET.
The field evidence is strong when you see the full picture. During a utility trial, moisture fell by 58% in the compartment fitted with Gas-Dry, from 66 to 28 ppmv. Over the same 89-day monitoring period, the two untreated compartments increased from 63 to 85 ppmv and from 55 to 66 ppmv. No outage was required.
A separate 200-litre SF₆ tank test with Gas-Dry Small recorded a reduction from 391 to 270 ppm in four days. These are separate tests, and drying rate depends on application and conditions.
FLEXIBLE FIT. READY FOR RE-USE.
Small and Large models, interchangeable lids and replacement media support different compartment requirements and continued use. Connections include DN8, DN20, Rectus, Aeroquip and JIC Flare; service kits are also available.
For teams reviewing moisture-management options: